LMB5L-40 RCBO 1P 40A 6kA 30mA 18mm
LMB5L-40 1P RCBO integrates overload, short-circuit and 30mA earth leakage protection in one compact module. C curve, 6kA breaking capacity, 230/240V 50/60Hz, DIN rail mount. Ideal for residential & light commercial socket circuits, monthly test button for safety check.
$8.00
Product Overview
LMB5L-40 RCBO is an integrated residual current circuit breaker with overcurrent protection (RCBO), combining miniature circuit breaker (MCB) and residual current device (RCD) into one compact 1P+N modular unit. It provides 3-in-1 protection against overload, short circuit and earth leakage.
Adopted high-precision electromagnetic trip system, this RCBO trips instantly once leakage occurs, effectively preventing electric shock hazards for human body. C curve characteristic is suitable for household and light commercial loads such as lighting, socket circuits, air conditioners and small power equipment. Standard 35mm DIN rail installation for easy assembly inside distribution boxes. Widely used in residential buildings, apartments, retail shops and small PV auxiliary power distribution systems.
Key Features
- 🛡️ Integrated 3 protections: Overload, short-circuit & earth leakage protection in single module
- ⚡ 6kA rated breaking capacity: Reliable breaking performance under short-circuit fault
- 🟢 30mA residual current trip: High sensitivity for personal electric shock protection
- 🟠 Monthly test button: Regular function test to guarantee safety performance
- 📏 Compact 1P+N modular design: Saves space inside consumer units
- 🔥 Flame retardant thermoplastic housing: High temperature resistance, anti-aging
- 📊 C-curve trip characteristic: Ideal for resistive & inductive loads
- 🌐 Wide frequency support: 50Hz / 60Hz compatible for global markets
- ✅ Certified design, stable & long service life
Technical Specifications
| Item | Parameter |
|---|---|
| Model | LMB5L-40 |
| Type | 1P+N RCBO |
| Rated Voltage | 230/240V AC |
| Frequency | 50/60Hz |
| Rated Current | C10, C16A, C20A, C25A, C32A, C40A |
| Residual Operating Current (IΔn) | 30mA |
| Rated Breaking Capacity | 6000A (6kA) |
| Trip Curve | C Curve |
| Mounting | 35mm standard DIN rail |
| Protection Class | IP20 (for inside distribution box) |
| Operation Temperature | -20℃ ~ +60℃ |
| Relative Humidity | ≤95% (non-condensing) |
| Altitude | ≤2000m |
Main Functions
- Overload Protection When load current exceeds rated value for a period, RCBO will automatically trip to prevent cable overheating and fire risk.
- Short Circuit Protection Instant trip when short-circuit fault occurs, quickly cut off power to protect wiring and upstream electrical equipment.
- Earth Leakage / Residual Current Protection Once leakage current reaches 30mA, the unit trips rapidly to protect users from fatal electric shock.
- Function Test Button (Orange T button) Press the orange TEST button monthly to verify the leakage protection function works normally.
⚠️ Note: Press test button only when circuit is powered on.
Installation Guide
⚠️ Installation must be carried out by qualified electrician, power off before wiring!
- Clip the RCBO onto standard 35mm DIN rail inside distribution box.
- Wiring: Top terminals for incoming power; Bottom terminals for outgoing load.
- L terminal for live wire, N terminal for neutral wire. Tighten all screws firmly, no bare copper exposed.
- After wiring, switch ON the handle, then press TEST button to check trip function.
- IP20, indoor use only, not for outdoor exposed installation.
Operation & Indication
- Switch handle UP = ON, power output available
- Switch handle DOWN = OFF / Tripped, power disconnected
- Orange
Tbutton: Monthly test for leakage protection - Green indicator window: Status display
If the breaker trips automatically: Check circuit overload, short circuit or earth leakage fault before re-closing. Do NOT force reset repeatedly without troubleshooting.
Safety Warnings
- High voltage inside, do not disassemble the product. Risk of electric shock.
- This RCBO cannot protect against overvoltage and undervoltage. Match with OVP if voltage protection is required.
- Press TEST button every month to confirm leakage protection function.
- Stop using immediately if housing cracks, melts or produces strange odor.
- Not for DC circuit application. For AC 230V only.
- Do not exceed rated current for long-term operation.
Packing List
LVMA LMB5L-40 RCBO × 1pc, Instruction manual ×1pc
Warranty
24 months warranty from manufacturing date under correct installation and normal operation. Warranty void for man-made damage, overload burnout, unauthorized disassembly and harsh environment usage.
Manufacturer: LVMA Certifications: CE / CB / ISO (customize as required)
You May Be Interested In…
User Notice
By accessing and using this store website, you acknowledge that you have read, understood and agreed to all terms below.
- Product Information
All product parameters, images, specifications and prices on the website are for reference only. Minor differences may exist due to photo lighting, production batches and product updates. Actual goods shall prevail over physical products and formal sales contracts. Prices are subject to change according to raw‑material costs and market conditions. Please confirm the latest quotation before placing orders. - Orders
Submitting an order does not constitute a binding contract. We will verify stock status, specifications and lead‑time. The order becomes valid only after our confirmation. In case of out‑of‑stock or specification errors, we will contact you for adjustment or order cancellation. - Payment, Shipping & Logistics
Please complete payment via agreed channels. Delivery time follows mutually confirmed lead‑time. Goods are shipped by third‑party logistics partners. Please inspect goods upon receipt. Report damage or loss during transportation immediately at the time of signing for the shipment. - Return & Warranty Policy
Custom‑made and special‑specification items cannot be returned or exchanged without quality issues. For confirmed quality defects, please provide photos or video evidence within the agreed period. We offer repair or replacement solutions under warranty terms. Damage caused by improper installation, misuse or human error is not covered by warranty. - Account & User Conduct
Keep your account credentials secure. All operations under your account are deemed authorized by you. Any fraudulent or infringing activities are prohibited. We reserve the right to restrict account access for violations. - Intellectual Property
All texts, images, logos and design materials on this site are protected by copyright. No reproduction, redistribution or commercial use is allowed without written permission. - Miscellaneous
We reserve the right to revise this User Notice. Updates will be posted on the website. Any disputes shall first be resolved through friendly negotiation between both parties.



Reviews
Clear filtersThere are no reviews yet.